Giersch MG10/2-M-L-N-LN 125–530 kW Modulating Gas Burner

Giersch MG10/2-M-L-N-LN 125–530 kW Modulating Gas Burner

Stokda var

Giersch MG10/2-M-L-N-LN is a modulating Low NOx forced-draught gas burner with an output range of 125–530 kW. It is designed for boilers, hot-water generators and compatible commercial or industrial heating equipment operating on natural gas.

The M designation identifies modulating operation, N indicates the natural-gas version and LN refers to the low-emission Low NOx design. Modulating control adjusts burner output according to the actual heat demand of the system.

When heat demand decreases, the burner reduces its output; when demand increases, output rises progressively. This reduces burner starts, pre-purge losses and start-up emissions while supporting stable boiler-water or process-temperature control.

The MG-LN series uses optimised airflow, a pressure-stable fan and a precision mixing system to maintain a consistent gas-to-air ratio. Its star-shaped mixing head is designed to reduce nitrogen-oxide emissions.

The MG10/2-LN is designed to meet EN 676 emission class 3 requirements. Giersch states a NOx limit of no more than 80 mg/kWh under the applicable test conditions.

Automatic burner management monitors ignition, flame presence and connected air and gas safety devices. A swivelling burner housing provides convenient access to the mixing head, ignition electrodes and service components.

Technical specifications:

  • Brand: Giersch
  • Official model: MG10/2-M-L-N-LN
  • Product type: forced-draught gas burner
  • Fuel: natural gas
  • Burner output: 125–530 kW
  • Operating mode: modulating
  • Emission technology: Low NOx
  • Emission class: EN 676 class 3
  • NOx limit: ≤80 mg/kWh
  • Electrical supply: 1/N/PE, 220–240 V, 50 Hz
  • External protection: 10 A
  • Motor power: 0.75 kW
  • Flame monitoring: ionisation electrode
  • Construction: monobloc forced-draught burner
  • Output control: linked gas-air modulation
  • Gas train: selected according to gas pressure and project requirements

Gas-train size, available inlet pressure, burner-head length and control equipment must be selected for the particular installation. Burner compatibility should be checked against both the boiler output and furnace-resistance working curve.