Giersch R30-AE Single-Stage Oil Burner
Giersch R30-AE Single-Stage Oil Burner
Giersch R30-AE is a single-stage forced-draught oil burner designed for commercial, residential and medium-capacity boiler systems. It operates with light heating oil EL complying with DIN 51603.
The burner covers an output range of 95–273 kW. At an assumed boiler efficiency of 92%, the corresponding boiler-output range is approximately 87–251 kW. The model is suitable for residential complexes, administrative buildings, production facilities, warehouses and medium-sized boiler rooms.
R30-AE operates at a single selected output and does not provide flame modulation or a separate second output stage. The AE designation identifies a start-up relief system that reduces the load during ignition.
During start-up, oil-pump pressure is initially limited to approximately 12 bar. After flame stabilisation, the pump changes to its main operating pressure of approximately 15 bar. This provides a more controlled transition to full output and helps reduce ignition impact.
The pressure-stable fan and precision mixing system provide the required mixture of fuel and combustion air. The flame is monitored by a QRB photoelectric sensor, while ignition and safety functions are managed by the LMO24 burner-control unit.
Main features:
• Brand: Giersch
• Model: R30-AE
• Product type: Forced-draught oil burner
• Operating mode: Single-stage with start-up relief
• AE function: Reduced start-up load
• Flame modulation: No
• Oil preheating: No
• Fuel: Light heating oil EL
• Fuel standard: DIN 51603
• Burner output: 95–273 kW
• Boiler output at ηk = 92%: 87–251 kW
• Fuel consumption: 8–23 kg/h
• Start-up pump pressure: Approximately 12 bar
• Main operating pressure: Approximately 15 bar
• Oil-pump capacity: 70 litres per hour
• Power supply: 1/N/PE, 230 V, 50 Hz
• Supply-voltage range: 220–240 V
• Motor output: 250 W
• Motor speed: Approximately 2850 rpm
• Maximum starting current: 2.8 A
• Operating current: Approximately 1.6 A
• Flame monitoring: QRB photoelectric sensor
• Burner-control unit: LMO24
• Sound level: Up to 73 dB(A)
• Emission class: 3
• NOx limit: Up to 120 mg/kWh
• Compliance standard: DIN EN 267
• Burner-tube diameter: 130 mm
• Burner-tube length: 260 mm
• Burner-body depth: Approximately 411 mm
• Overall depth: Approximately 671 mm
• Height and width: Approximately 446 × 446 mm
• Overall dimensions: Approximately 446 × 446 × 671 mm
• Mounting-hole circle: 170–200 mm
• Flange outside diameter: 220 mm
• Fixing: M8
• Approximate weight: 29 kg
• Current product number: 13-36-40835
• Country of manufacture: Germany